← All calculatorsEngineering

Voltage Drop

Over a long cable run the conductor's own resistance consumes part of the supply voltage, so equipment at the far end sees less than the source provides. This calculator quantifies that loss so you can decide whether to increase conductor size.

Voltage drop
6.35 V
% drop on 120V
5.29%

How to use the Voltage Drop

  1. Enter the one-way run length; the calculation doubles it for the return path.
  2. Enter the load current in amps and the system voltage.
  3. Enter the conductor cross-section in mm² or select an AWG size.
  4. Compare the percentage drop against the limit in your wiring regulations.

How the calculation works

The current travels out and back, so the resistance in circuit is twice the one-way length divided by the cross-sectional area, scaled by the material's resistivity. Copper at 20 °C is about 1.72 × 10⁻⁸ Ω·m; aluminium is roughly 1.6 times more resistive, which is why aluminium runs need a larger conductor for the same drop.

Installation standards cap the drop rather than the absolute volts. Common practice allows around 3% for a final circuit and 5% overall from origin to load, because excessive drop causes motors to run hot, lighting to dim and electronics to reset. Resistivity also rises with temperature, so a cable running warm inside insulation drops more than a cold-calculation suggests.

Formula
V_drop = 2 × ρ × L × I / A (single-phase; ×√3 rather than 2 for three-phase line-to-line)

Source: Copper resistivity 1.72 × 10⁻⁸ Ω·m at 20 °C; drop limits per IEC 60364 / NEC 210.19 recommendations. VERIFY the limit in your local wiring regulations.

Worked example

A 16 A load on a 230 V single-phase supply, 42 m from the board, wired in 2.5 mm² copper.

  1. Circuit length = 2 × 42 = 84 m.
  2. R = 1.72e−8 × 84 / 2.5e−6 = 0.578 Ω.
  3. V_drop = 16 × 0.578 = 9.25 V.
  4. As a percentage: 9.25 / 230 = 4.02%.

About 9.25 V dropped, or 4% — over the usual 3% final-circuit guidance, so step up to 4 mm².

Frequently asked questions

What voltage drop is acceptable?+

Typically 3% on a final circuit and no more than 5% from the supply origin to the load, though the exact figures are set by your national wiring regulations and by equipment tolerance.

Why is the run length doubled?+

Current flows to the load and back, so both conductors contribute resistance. Using the one-way length halves the calculated drop and produces an undersized cable.

Does this apply to DC systems like solar or 12 V vehicles?+

Yes, and it matters more at low voltage: a 1 V drop is 0.4% of 230 V but 8% of 12 V. Low-voltage runs usually need conductors far larger than the current alone would suggest.

Should I use the cold or hot resistivity?+

Calculate at operating temperature for a realistic result. Copper resistance rises roughly 0.39% per °C, so a conductor at 70 °C drops about 20% more voltage than the same one at 20 °C.

Reviewer note — verify: Permitted voltage drop percentages differ between IEC, NEC and national annexes — confirm against the regulations governing the installation.

Last reviewed August 31, 2026. We review this page whenever the underlying formula, tax year, published rate or standard changes.

Related

More in Engineering